Johnson Controls Unitary Products 697936-UIM-B-01211RESIDENTIAL GAS FURNACE MODELS: TM9X*MP – High Efficiency Motor(95.5% AFUE Single Stage Multi-posi
697936-UIM-B-0121110 Johnson Controls Unitary ProductsSIDE RETURNLocate the “L” shaped corner locators. These indicate the size of the cut-out to be m
697936-UIM-B-01211Johnson Controls Unitary Products 11The furnace must be isolated from the gas supply piping system byclosing its individual external
697936-UIM-B-0121112 Johnson Controls Unitary ProductsSECTION V: ELECTRICAL POWERELECTRICAL POWER CONNECTIONSField wiring to the unit must be grounded
697936-UIM-B-01211Johnson Controls Unitary Products 13For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” do
697936-UIM-B-0121114 Johnson Controls Unitary Products FIGURE 19: Thermostat Chart - Single Stage HP with Single Stage Furnaces Single Stage Hea
697936-UIM-B-01211Johnson Controls Unitary Products 15ACCESSORY CONNECTIONSThe furnace control will allow power-switching control of various acces-sor
697936-UIM-B-0121116 Johnson Controls Unitary ProductsCONDENSATE DRAIN TERMINATIONA condensate sump pump MUST be used if required by local codes, orif
697936-UIM-B-01211Johnson Controls Unitary Products 17 FIGURE 22: Upflow ConfigurationINDUCER ROTATED FORLEFT SIDE VENTINGUPFLOWAS RECEIVEDINDUCER RO
697936-UIM-B-0121118 Johnson Controls Unitary Products FIGURE 23: Downflow ConfigurationAIRFLOWAIRFLOWMove raingutter hoseto this positionDOWNFLOW -
697936-UIM-B-01211Johnson Controls Unitary Products 19 FIGURE 24: Horizontal Left ConfigurationHORIZONTAL - LEFTINDUCER ROTATEDHORIZONTAL - LEFTINDUC
697936-UIM-B-012112 Johnson Controls Unitary ProductsSECTION I: SAFETYThis is a safety alert symbol. When you see this symbol onlabels or in manuals,
697936-UIM-B-0121120 Johnson Controls Unitary Products FIGURE 25: Horizontal Right ConfigurationAIRFLOWHORIZONTAL - RIGHTINDUCER ROTATEDHORIZONTAL -
697936-UIM-B-01211Johnson Controls Unitary Products 21SECTION VII: COMBUSTION AIR AND VENT SYSTEMCOMBUSTION AIR AND VENT SAFETYThis Category IV, dual
697936-UIM-B-0121122 Johnson Controls Unitary Products Dimensions are those required in Standard ASTM D-3311.Example:An 80,000 BTUH furnace requires 3
697936-UIM-B-01211Johnson Controls Unitary Products 23VENT CLEARANCES† A vent shall not terminate directly above a sidewalk or paved driveway that is
697936-UIM-B-0121124 Johnson Controls Unitary ProductsVENT SYSTEMThis furnace is certified to be installed with one of two possible ventconfigurations
697936-UIM-B-01211Johnson Controls Unitary Products 25DOWNWARD VENTINGIn some applications, it may be necessary to run the vent pipe and airintake dow
697936-UIM-B-0121126 Johnson Controls Unitary ProductsAn unconfined space is not less than 50 cu.ft (1.42 m3) per 1,000BTU/hr (0.293 kW/h) input rati
697936-UIM-B-01211Johnson Controls Unitary Products 27Air Supply Openings and Ducts1. An opening may be used in lieu of a duct to provide to provide t
697936-UIM-B-0121128 Johnson Controls Unitary ProductsSpecially Engineered InstallationsThe above requirements shall be permitted to be waived where s
697936-UIM-B-01211Johnson Controls Unitary Products 29GAS PIPING LEAK CHECKIt is recommended that when the gas supply is first connected to thefurnace
697936-UIM-B-01211Johnson Controls Unitary Products 3• Furnaces for installation on combustible flooring shall not beinstalled directly on carpeting,
697936-UIM-B-0121130 Johnson Controls Unitary ProductsTable 14: Gas Rate (CU FT/HR) at Full InputSeconds For 1 RevolutionSize of Test DialSeconds For
697936-UIM-B-01211Johnson Controls Unitary Products 31ADJUSTMENT OF MANIFOLD GAS PRESSURE & INPUT RATEInlet and manifold gas pressure may be measu
697936-UIM-B-0121132 Johnson Controls Unitary ProductsADJUSTMENT OF TEMPERATURE RISEAfter about 5 minutes of operation, determine the furnace temperat
697936-UIM-B-01211Johnson Controls Unitary Products 33NOTES:1. Airflow expressed in standard cubic feet per minute (CFM).2. Motor voltage at 115 V.SEC
697936-UIM-B-0121134 Johnson Controls Unitary ProductsPRESSURE SWITCHESThis furnace is supplied with two pressure switches, which monitor theflow thro
697936-UIM-B-01211Johnson Controls Unitary Products 35STEADY ON ANY COLOR: Control failure. Turn power to the furnaceoff and back on. If the fault cod
697936-UIM-B-0121136 Johnson Controls Unitary ProductsSECTION XI: REPLACEMENT PARTS LISTDESCRIPTIONMOTORBLOWER, COMBUSTIONMOTOR, DIRECT DRIVE BLOWEREL
697936-UIM-B-01211Johnson Controls Unitary Products 37SECTION XII: WIRING DIAGRAM FIGURE 41: Wiring DiagramLEGENDDSDoorswitch MOTCirculatin
Subject to change without notice. Published in U.S.A. 697936-UIM-B-01211Copyright © 2011 by Johnson Controls, Inc. All rights reserved. Supersedes: 69
697936-UIM-B-012114 Johnson Controls Unitary ProductsINSPECTIONAs soon as a unit is received, it should be inspected for possible dam-age during trans
697936-UIM-B-01211Johnson Controls Unitary Products 5SECTION II: DUCTWORKDUCTWORK GENERAL INFORMATIONThe duct system’s design and installation must:1.
697936-UIM-B-012116 Johnson Controls Unitary ProductsCOIL INSTALLATIONCOIL/FURNACE ASSEMBLY - MC/FC/PC SERIES COILSFURNACE ASSEMBLY - MC & FC SERI
697936-UIM-B-01211Johnson Controls Unitary Products 7Dimension “C” should be at least 2/3 of dimension “D”. See Figure 6.CRITICAL COIL PROJECTIONThe c
697936-UIM-B-012118 Johnson Controls Unitary ProductsHORIZONTAL APPLICATIONATTIC INSTALLATIONThis appliance is certified for line contact when the fur
697936-UIM-B-01211Johnson Controls Unitary Products 9SECTION III: FILTERSFILTER INSTALLATIONAll applications require the use of a field installed filt